Avici Systems Inc.


Preliminary Customer Site Survey

This section includes the information gathered in a site survey. Before scheduling a TSR system installation, contact your sales representative and schedule a site preparedness survey.

NOTE This is a preliminary survey form. While you may fill out as much as possible prior to meeting with an Avici representative, the survey will not be finalized without a full onsite inspection with an Avici representative prior to shipping equipment.

Customer:  

Location:  

Technical Contact:  

Telephone Number:  

Receiving Contact:  

Telephone Number:  

Avici Sales Contact:  

Avici CSE Representative:  

Ship to Address:  

Contact at Installation Site:  

(Fill out a form for each installation location and attach with this form.)

Telephone Number:  

Site Staffed Hours:  

Site Address:  

Interface type(s):  

Single-mode

Multi-mode

(Enter quantity of each.)

  • OC-3c short reach (500 Km)

N/A

  • OC-3c intermediate reach (15 Km)

N/A

  • OC-12c short reach (500 m)

N/A

  • OC-12c intermediate reach (15 Km)

N/A

  • OC-48c short reach (2 Km)

N/A

  • OC-198c short reach

N/A

  • Gigabit Ethernet long reach

  • Gigabit Ethernet short reach

N/A

Local Union or Certification:  

Requirements of an Installer:  

Power Requirements

q

Meets power requirements: Input power -0 to 48 Vdc nominal 5500 W max.

Will power cable leads approach the TSR system from above or below the planned location? _______________

q

Customer supplies power feeds and returns. Total of eight supply and eight return feeds, size determined by local code requirements.

q

Customer supplies ground wire (#6 AWG) for single point ground to facility ground.

Transport & Unpacking

q

Customer provides accessible loading dock location (Include hours of operation of the loading dock).

q

Do delivery, freight elevators, and access to receiving dock need to be scheduled with building management?

Name and contact number of person who can coordinate use of the receiving platform for delivery of TSR system?

Restrictions in truck size to be used for delivery:

q

Customer provides pallet jack, forklift or similar equipment for transporting the bay from the loading dock to the installation area.

q

Heights and widths of all hallways and doorways en route to the installation site exceed the required measurements of the bay.

  • Height on installation dolly: 2191 mm (86.3 in.)

  • Height on pallet (uncrated): 2337 mm (92 in.)

  • Height without shipping pallet or dolly: 2178 mm (85.8 in.)

  • Width on shipping pallet 1016 mm (40 in.)

  • Width on installation dolly 813 mm (32 in.)

q

Note raised thresholds or obstructions en route to installation site:

__________________________________________________________________________________________

q

Determine slope of any ramps onto a raised floor or other area.

q

Note if floor surface en route to installation site is not smooth.

Floor Loading

q

Floor loading: fully loaded bay provides floor loading of 586 kg/m2 (120 lb/ft2) given minimum access aisles in front and behind.

q

Concrete floors must be a minimum of 6 inches thick, 3000 psi concrete for anchoring the bay. The drilled hole depth must be 4 in.

q

Raised floors require a pedestal. Measure the space below floor tiles. Select a pedestal size.

12 in. ___         18 in. ___         Custom (provide measurement): ________________________________

Installation

q

Customer has determined location to install TSR system.

q

Installation provides sufficient room for TSR system including front and back aisles.

q

Is there fixed (bolted) equipment on either side of the TSR system? (If so, equipment may need to be temporarily moved to accommodate pedestal installation.): (yes/no) _________

q

For raised floor installations, location below installation site is free of cables and other equipment.

Environment

q

Meets cooling requirements: 4.93 kW/m2 (458 kW/ft.2) assuming 48 in. front and 24 in. rear aisles. Max dissipation per bay is 5500 W.

q

Meets temperature requirements: long term: 5° to 40°C (41° to 104°F) short term: -5° to 50°C (23° to 122°F)

q

Meets humidity requirements: long term: 5% - 85% R. H., short term: 0% - 90% R. H. for 96 hours max.

Fiber

What are the fiber optic transmit and receive levels of equipment that will connect to the TSR system? Please specify: _________________

Will fiber optic cable leads approach the TSR system from above or below the planned location? ______________

Please return the completed form to: Avici Systems Inc.
Client-Services (PSO)
101 Billerica Ave.
N. Billerica, MA 01862


Copyright © 2001 Avici Systems Inc.